LED OPL and UniLinc Troubleshooting
50.Close Door Indication
Is there 24 volts AC at
H6-1 to H6-9?
Is there 24 volts AC at
H6-8 to H6-9?
Check Transformer
and Fuse F3.
Replace
I/O Board (AP1).
Replace
I/O Board (AP1).
Check harness and
loading door switch.
Repair or replace
as required.
No
Yes
Yes
Yes
Yes
Yes
No
TMB2380S
NOTE: Before proceeding, check the lint door, loading doors and switches for proper mechanical operation.
Is there 24 volts AC at
H6-2 to H6-9?
No
No
Check harness and
lint door switch.
Repair or replace
as required.
No
Is there 24 volts AC at
H6-3 to H6-9 with loading
door and lint doors
closed?
Is there 24 volts AC at
H6-4 to H6-9 with both
doors closed?
Yes
Check harness.
Replace harness
or I/O Board (AP1).
as required.
No
Yes
(1)
(2)
(3)
(5)
Is there 5 volts DC at
H3-6 to H3-11 closest to the
front-end control with loading
door open and 0 volts DC
with loading door
closed?
Check harness and
I/O Board (AP1).
Repair or replace
as required.
No
Is there 5 volts DC
at H3-18 to H3-11 with either
loading or lint door open and
0 volts DC with both
doors closed?
(6)
(4)
CAUTION: Always power down the machine
PRIOR to disconnecting or connecting the
H3 harness. Once disconnected, you can
power up the machine for troubleshooting.
Failure to do so may damage the front-end control.
NOTE: The following checks are DC
Voltage checks.
(7)
Replace front-end
control (AP2).
NOTE: If the voltage is present but
lower than 24 volts AC, ensure the
correct transformer configuration
jumper is installed.
TMB2380S