58.Fan Motor Contactor Error
Is there 24 volts AC
at H6-1 to H6-9?
Is there 24 volts AC
at H2-6 to H6-9?
Check Transformer
and Fuse F3.
Replace
I/O Board (AP1).
Check harness and
wire connections at
the motor contactor.
Repair or replace
as required.
No
Yes
Yes
Yes
Yes
No
NOTE: Before performing these checks, the airflow switch must be pulled in, and the motor must be running.
NOTE: If the voltage is present but
lower than 24 volts AC, ensure the
correct transformer configuration
jumper is installed.
Is there 24 volts AC at
H2-4 to H6-9 with fan
motor running?
No
Check control harness
H3 and I/O Board (AP1).
Replace as required.
No
Is there
5 volts DC at H3-8
to H3-11 with motor
contactor not engaged and
0 volts DC with motor
contactor
engaged?
(1)
(2)
(3)
(4)
CAUTION: Always power down the machine
PRIOR to disconnecting or connecting the
H3 harness. Once disconnected, you can
power up the machine for troubleshooting.
Failure to do so may damage the front-end control.
NOTE: The following checks are DC
voltage checks.
Replace front-end
control (AP2).