Installation
15
1800001
Exhaust Requirements
Whenever possible, install the finisher along an
outside wall where duct length can be kept to a
minimum and make-up air can be easily accessed.
Construction must not block the airflow at the rear of
the finisher. Doing so would cause inadequate air
supply to the finisher combustion chamber.
IMPORTANT: Provisions must be made for make-
up air.
IMPORTANT: Do not obstruct flow of combustion
and ventilation air.
Using the shortest possible path, connect the exhaust
outlet to an outlet duct. For gas models, use two
separate outlets.
IMPORTANT: Outlet ducts used for the finisher’s
exhaust may under no circumstances be shared
with other devices.
Finisher produces combustible lint. To
reduce the risk of fire, the finisher must be
exhausted to the outdoors.
To reduce the risk of fire and accumulation
of combustible gases, DO NOT exhaust
finisher air into a window well, gas vent,
chimney or enclosed, unventilated area
such as an attic wall, ceiling, crawl space
under a building, or concealed space of a
building.
W679
WARNING
Do not connect vents together. Gas and
ventilation outlets must be separate to
prevent fire.
Insulate all ducts to prevent fire.
W680
WARNING
Exhaust Requirements
Vapor Exhaust 206 cfm
Vapor Exhaust
(Inches of Water Column)
2.4 in.
Exhaust Roll Duct*
3 in. (75 mm)
*For ducts longer
than 15 ft. (4.57 m)
continue with
3.5 in. (90 mm)
Table 7